1The FREE chlorine residual must be at least ___ mg/L at the entry point of the distribution system.
0.2
2Water levels in wells must be tested...
weekly
3The TOTAL chlorine residual must be at least ___ mg/L at the entry point of the distribution system.
1.0
4At a minimum, the FREE or TOTAL chlorine residual must be _____________ throughout the distribution system.
Detectable
5A groundwater system that add chlorine must measure chlorine residual a least ___ times per week.
2
6A surface system that add chorine must measure chorine residual _______.
daily
7MRDL stands for Maximum Residual __________ Level.
Disinfection
8MRDL for chlorine and chloramine = ____ mg/L
4.0
9mg/L is equal to Parts Per __________
Million
10MRDL for chlorine dioxide = ___ mg/L
0.8
11MCL stands for Maximum __________ Level
Contaminant
12MCL for fluoride = ___ mg/L
4.0
13MCL for secondary fluoride = ____ mg/L
2.0
14The DNR states the acceptable range for ____________ is 0.6 - 0.8 mg/L
fluoride
15The DNR states the optimum fluoride level is ____ mg/L
0.7
16A system that adds fluoride must test it's fluoride concentration at least __________.
daily
17If a bacti sample is positive, three repeat samples must be taken at the following locations:
1. Original location (1 sample)
2. Within ____ services upstream and down stream of original location (2 samples)
5
18A system that adds fluoride must submit a sample to a state lab for testing at least _________ and compare their own test results to the state results ("split sample").
monthly
19MCL for TTHM (trihalomethanes) is ______ mg/L
0.08
20MCL for HAA5 (haloacetic acids) is _____ mg/L
0.06
21A bottle used to collect water for a bacteria ("bacti") test must ALWAYS contain powdered sodium thiosulfate ("THIO") to neutralize any __________ in the sample.
chlorine
22A bottle used to collect water for a fluoride (SPADNS) test must NEVER contain ______________.
sodium thiosulfate
23Sodium thiosulfate is also called...
THIO
24This test is used to measure the chlorine residual via spectrophotometry.
DPD
25This test is used to measure fluoride via spectrophotometry.
SPADNS
26How many buffers are needed at a MINIMUM to calibrate a pH meter?
2
27The Langelier Index is a measure of the water's ________________.
corrosivity
28The water is considered corrosive if the Langelier Index is...
below -2
29The water is considered ________________ if the Langelier Index is -2 to 0.
slightly corrosive
30The water is considered non-corrosive if the Langelier Index is _____ or greater.
0
31The minimum number of monthly bacteria ("bacti") samples that must be taken is determined by the system's....
population
32The total coliform MCL for systems that take less than 40 samples per month is _________ positive sample.
1
33The total coliform MCL for systems that take 40 or more samples per month is _________ positive samples.
5%
34A bacti sample must be tested within ____ hours of collection.
30
35Bacti samples not analyzed immediately must be kept at ___________ deg F (range).
40-50
36Bacti samples not analyzed immediately must be kept at ___________ deg C (range).
4-10
37Exceeding the total coliform MCL requires a ________ __________ within 24 hours, in addition to resampling.
public notice
38Two bacti samples 24 hours apart are required UNLESS the chlorine residual is tested after passing the first sample and is greater than _____ mg/L.
0.1
39_____________ bacteria are also called "indicator bacteria" because they indicate a POTENTIAL fecal contamination.
Coliform
40MCL for nitrate is ____ mg/L
10
41Secondary standard for iron (Fe) is ______ mg/L
0.3
42Secondary standard for manganese (Mn) is ______ mg/L
0.05
43Secondary standard for hydrogen sulfide (H2S) is ______ mg/L
0
44Secondary standard for bromate (BrO3) is ______ mg/L
0.01
45How often are bacti tests required to be taken from raw water (ie. directly from the well before any treatment)?
quarterly
46A Langelier Index above zero is considered _________-forming.
scale
47A sampler should never set down the bottle cap while taking a ________ ___________ sample.
total coliform
48Swing/swivel faucets, plastic faucets, aerated faucets, and threaded faucets are examples of bad locations to take a _____ __________ sample.
total coliform
49"________ bore, _______ end" describes faucets that are ideal for sampling total coliform.
smooth
50If a bacti sample for a groundwater system is positive, a "triggered source water" sample must be collected from all _______ that supply water to the sampling location.
wells
51Fluoride levels that exceed the MCL can result in ___________ (tooth staining) in children.
fluorosis
52Accurate liquid measurement requires reading the bottom of the meniscus at _____ _________.
eye level
53Nitrate monitoring requires one sample from each entry point every....
year
54The frequency of lead & copper monitoring samples is determined by...
population
55Synthetic organic chemicals must be sampled from each entry point _________ times a year.
four
56For systems serving 10K+ people and chlorinated, total trihalomethanes must be sampled once every...
quarter
57Volatile organic compounds must be sampled once every...
quarter
58Radioactivity must be monitored once every....
four years