The low pressure cutout switch is operated by:
a. a magnet
b. a bellows
c. spring tension
d. water pressure
b. a bellows
2
A good refrigerant should be
a. nonpoisonous
b. non-explosive
c. non-flammable
d. all of the above
d. all of the above
3
If a refrigerating system extracted 48
800 btu per hour
4
The purpose of the low-pressure cutout switch is to
a. maintain liquid refrigerant at the suction of the compressor
b. maintain a present suction pressure to the compressor
c. cut out the compressor at set pressure
d. cut compressor in and out at a present pressure
d. cut compressor in and out at a present pressure
5
The most likely cause of high superheat would be
a. too much refrigerant
b. expansion valve open too wide
c. expansion valve closed in too much
d. back-pressure valve set too high
c. expansion valve closed in too much
6
The purpose of the evaporator is to
a. absorb latent heat of vaporization
b. absorb latent heat of fusion
c. transfer latent heat of vaporization
d. transfer latent heat of fusion
a. absorb latent heat of vaporization
7
Air is removed from the system by
a. increasing the amount of cooling water
b. opening the purge valve
c. running the refrigerant through an aerator
d. running the refrigerant through a deaerotor
b. opening the purge valve
8
The suction pressure switch is operated by
a. electric current
b. thermocouple
c. pressure on bellows
d. a relay cutout
c. pressure on bellows
9
A hot suction line might be caused by
a. insufficient refrigerant
b. insufficient lubrication
c. expansion valve closed too much
d. too much refrigerant
a. insufficient refrigerant
10
The device used for low-pressure control and high-pressure cutout on a compressor is called a
a. cutout
b. pressure controller
c. controller switch
d. cutout switch
b. pressure controller
11
Thermal expansion valves are usually of the
a. bellows type
b. magnetic type
c. diaphragm type
d. A or C
d. A or C
12
Liquid reaching the compressor through the suction line is called
a. flooding back
b. superheating
c. overflowing
d. recycling
a. flooding back
13
Pressure controllers are usually of the
a. diaphragm-type construction
b. bellows-type construction
c. magnetic-type construction
d. pilot-valve type construction
b. bellows-type construction
14
If the cooling water to the condenser should suddenly fail
a. the solenoid valve will close
b. the expansion valve will close
c. the compressor will shut down
d. an alarm will ring to notify the engineer
c. the compressor will shut down
15
If the solenoid valve closed by accident
the compressor would be stopped by the
a. low-pressure cutout switch
b. high-pressure cutout switch
c. low-water cutout switch
d. automatic trip
16
The solenoid valve controls the
a. amount of refrigerant entering the evaporator coils
b. amount of refrigerant going to the expansion valve
c. amount of refrigerant going to the compressor
d. pressure of the refrigerant going to the evaporator coils
b. amount of refrigerant going to the expansion valve
17
As Freon passes through the expansion valve
a. the volume decreases and the pressure increases
b. the volume increases and the pressure increases
c. the pressure decreases and the volume increases
d. the volume decreases and the pressure decreases
c. the pressure decreases and the volume increases
18
When checking zinc plates in a condenser
one should
a. paint the plates with red lead
b. install all new plates
c. clean the plates and renew worn-out ones
d. ground each plate to the shell
19
if the compressor short cycles on high pressure cutout
which of the following eould you check?
a. the user system is getting cooling water
b. if plenty of cooling water is running through but it is not picking up heat
20
In a refrigerating system the temperature is at its highest between the
a. condenser and receiver
b. compressor and condenser
c. receiver and evaporator
d. evaporator and compressor
b. compressor and condenser
21
A Freon unit will tend to short cycle when operating under
a. heavy loads
b. normal conditions
c. light loads
d. all of the above
c. light loads
22
Short-cycling means that the machine
a. grounds out frequently
b. stops and starts frequently
c. runs too fast
d. runs too slow
b. stops and starts frequently
23
Freon is
a. non-corrosive
b. flammable
c. nontoxic
d. A and C
d. A and C
24
A refrigerant should have a
a. high latent heat
b. high sensible heat
c. low latent heat
d. low sensible heat
a. high latent heat
25
A method of reducing capacity without reducing compressor speed is called
a. low-pressure bypassing
b. high-pressure bypassing
c. hot-gas bypassing
d. short-cycling
c. hot-gas bypassing
26
The thermal expansion valve responds to the
a. amount of superheat in the vapor leaving the coil
b. amount of superheat in the liquid
c. temperature in th e evaporator coils
d. pressure in the evaporator coils
a. amount of superheat in the vapor leaving the coil
27
The bulb for the thermal expansion valve is located
a. in the middle of evaporator coils
b. near the evaporator coil outlet
c. near the evaporator coil inlet
d. on the bottom row of evaporator coils
b. near the evaporator coil outlet
28
A thermostat is a
a. temperature-operated switch
b. pressure-oriented switch
c. super-heat operated switch
d. back-pressure operated switch
a. temperature-operated switch
29
The elements of thermostat switch are usually of the
a. diaphragm type
b. bimetal type
c. valve type
d. pilot-valve type
b. bimetal type
30
When heavy electrical currents are involved
the thermostat will be operated by
a. small circuit breaker
b. pressure pipe
c. fusetron
d. relay
31
If the compressor runs continually
the cause might be the
a. high-pressure cutout switch is jammed open
b. low-pressure switch is jammed about
c. thermal bulb is not operating properly
d. scale trap is clogged
32
The solenoid valve can be typed as a
a. thermal valve
b. magnetic stop valve
c. bellows valve
d. bimetallic valve
b. magnetic stop valve
33
If the compressor had been running satisfactory
for a long period of time but the coil level was rising slowly
34
If the compressor had been running satisfactory for a long period of time but suddenly the compartment temperature started to rise
the trouble might be
a. the solenoid valve is jammed shut
b. the expansion valve may have water frozen in it
c. a refrigerant leak has developed
d. any of the above
35
When charging a Freon system
all the valves should be in their normal position except the
a. expansion valve
b. purge valve
c. king valve
d. solenoid valve
36
Abnormal discharge temperatures would be caused by
a. leaky suction valves
b. leaky discharge valves
c. faulty piston rings
d. any of the above
d. any of the above
37
A device for holding open the suction valve and drawing gas from the suction manifold and returning it to the suction line without compressing is is called
a. discharge line bypass
b. cylinder unloader
c. suction line bypass
d. relief valve
b. cylinder unloader
38
As heat is removed open the suction valve and drawing gas from the suction manifold and returning it to the suction line without compressing it is called
a. perfect zero
b. double zero
c. absolute zero
d. cold zero
c. absolute zero
39
The boiling point of water in an open container at sea level is 212⁰F. If the pressure on the open container is decreased
such as going up to the top of a mountain
40
Another name for the liquid valve is the
a. master valve
b. king valve
c. Freon valve
d. shutoff valve
b. king valve
41
If the temperature in the icebox is too high
the trouble could be
a. a clogged scale trap
b. air in the system
c. automatic controls not functioning properly
d. insufficient cooling water to the condenser
42
Oil is added to a Freon compressor by
a. pouring through oil hole in base
b. pumping in with a hand pump
c. pumping in with an electric-driven pump
d. shutting down the machine and pouring in through the crankcase inspection plate opening
b. pumping in with a hand pump
43
If no gaskets are used in the piping joints of a Freon system
the joints must be
a. finished joints
b. welded joints
c. ground joints
d. soldered joints
44
When adding oil to a Freon system one must be sure that
a. all air is removed from the pump and fittings
b. there is too high suction pressure
c. the discharge pressure is too high
d. the condenser is shutdown
a. all air is removed from the pump and fittings
45
If the head pressure is too high
a. the relief valve should open before the high-pressure cutout
b. the relief valve should open and let excess refrigerant valve opens
c. the high-pressure cutout switch should operate before relief vakve opens
d. close in on the suction valve
c. the high-pressure cutout switch should operate before relief valve opens
46
If the compressor-discharge temperature is higher than the receiver temperature
a. increase the amount of cooling water to the condenser
b. decrease the amount of cooling water to the condenser
c. add more refrigerant to the system
d. remove some of the refrigeration from the system
b. decrease the amount of cooling water to the condenser
47
The dehydrator is used
a. to remove moisture from the system
b. to remove air from the system
c. when adding refrigerant to the system
d. A and C
d. A and
48
If the discharge side of the thermal expansion valve is warmer than the inlet side
the
a. expansion valve is working normally
b. expansion valve is not working normally
c. solenoid valve is not working normally
d. scale trap is dirty
49
The oil level in the compressor should be checked
a. while the compressor is in operation
b. just before starting the compressor
c. after a long period of operation
d. B and C
d. B and C
50
The relief valve is located on the
a. discharge side of condenser
b. discharge side of compressor
c. outlet of the evaporator coils
d. receiver tank
b. discharge side of compressor
51
The expansion valve on a Freon system controls the
a. superheat of the gas leaving the compressor
b. back pressure in the evaporator
c. temperature of the icebox
d. superheat of the gas leaving the evaporator
d. superheat of the gas leaving the evaporator
52
Thw scale trap is located between the
a. king valve and the expansion valve
b. solenoid valve and expansion valve
c. evaporator and receiver
d. compressor and evaporator
a. king valve and the expansion valve
53
If the high-pressure switch on the compressor opens and stops the compressor
a possible cause could be
a. too much cooling water going through the condenser
b. not enough refrigerant in the system
c. a leak in the evaporator cells
d. not enough cooling water going through the condenser
54
The capacity of a refrigerant unit can be regulated by
a. changing the speed of the compressor
b. changing the amount of cooling water to the condenser
c. changing the amount of refrigerant in the system
d. any of the above
d. any of the above
55
which of the following would not cause high suction pressure?
a. insufficient refrigeration
b. leaky suction valves
c. expansion valve stuck open
d. suction valve not adjusted properly
a. insufficient refrigeration
56
All of the following are alloys of nickel except
a. K-monel
b. Inconel-X
c. Chromium molybdenum steel
d. Nichrome
c. Chromium molybdenum steel
57
If the compressor runs continuously
the cause might be a
a. defective thermal valve
b. clogged scale trap
c. stuck high pressure switch
d. stuck low-pressure switch
58
Dairy products should be kept at temperature of
a. 10⁰ to 20⁰
b. 20⁰ to 30⁰
c. 35⁰ to 45⁰
d. 15⁰ to 25⁰
c. 35⁰ to 45⁰
59
The purpose of the expansion valve bypass is to
a. increase the efficiency of the plant
b. increase the capacity of the evaporator
c. control the refrigerant to the evaporator in case the automatic valves fall
d. bypass the compressor
c. control the refrigerant to the evaporator in case the automatic valves fall
60
Frost on the outside of the thermal expansion valve may be caused by
a. king valve and the expansion valve
b. receiver and the condenser
c. compressor and the receiver
d. evaporator coils and the compressor
c. compressor and the receiver
61
The charging valve is located between the
a. king valve and the expansion valve
b. receiver and the condenser
c. compressor and the receiver
d. evaporator coils and the compressor
a. king valve and the expansion valve
62
A high suction pressure and a cold crankcase indicate
a. air in the system
b. leaky suction valves
c. expansion valve open too wide
d. B or C
d. B or C
63
A high temperature in the icebox could not be caused by
a. insufficient refrigeration
b. air in the system
c. expansion valve open too wide
d. too much refrigerant in the system
c. expansion valve open too wide
64
When securing a Freon system for repairs
a. pump down to 1 or 2lbs pressure
b. pump down to a slight vacuum
c. pump down tob10 tob15 kbs pressure
d. remove all refrigerant from the system
a. pump down to 1 or 2lbs pressure
65
The solenoid valve is located between the
a. scale trap and the thermal expansion valve
b. thermal expansion valve and the evaporator
c. king valve and the scale trap
d. automatic and manual expansion valves
a. scale trap and the thermal expansion valve
66
When starting a refrigeration system
always
a. vent the condenser
b. vent the evaporator
c. bypass the condenser
d. none of the above
67
Before securing a compressor to do maintenance work on it
be sure to
a. have gas mask handy
b. notify the captain
c. make arrangements to have perishables taken care of
d. A and C
68
212⁰F is equal to
a. 106⁰C
b. 110⁰C
c. 100⁰F
d. 100⁰C
d. 100⁰C
69
A good refrigerant should
a. have a low boiling point
b. have a high latent heat
c. be able to be liquified at normal seawater temperatures
d. all of the above
d. all of the above
70
140⁰F is equivalent to
a. 50⁰C
b. 60⁰C
c. 40⁰C
d. 55⁰C
b. 60⁰C
71
70⁰C is equivalent to
a. 150⁰F
b. 160⁰F
c. 158⁰F
d. 155⁰F
c. 158⁰F
72
Low suction pressure is caused by
a. air in the system
b. leaky compressor suction valves
c. solenoid valve not functioning properly
d. expansion valve causing flooding back
c. solenoid valve not functioning properly
73
The charging connection in a refrigerating system is located
a. before the receiver
b. between the condenser and the receiver
c. between the receiver and the king valve
d. between the king valve and the solenoid valve
d. between the king valve and the solenoid valve
74
Water tube boilers have
a. one fusible plug
b. no fusible plugs
c. two fusible plugs
d. none of the above
b. no fusible plugs
75
The valve that prevents water from backing out of the boiler into the feed line is the
a. bottom blow valve
b. skin valve
c. feed-check valve
d. feed-stop valve
c. feed-check valve
76
The fuel oil heater is located
a. on the discharge side of the service pump
b. on the suction side of the service pump
c. on the discharge side of the transfer pump
d. between the settling tank and the service pump
a. on the discharge side of the service pump
77
Boilers"pulsations" are caused by
a. too high fuel pressure
b. insufficient air
c. forcing the boiler beyond capacity
d. all of the above
d. all of the above
78
In the forced draft system
a. each furnace has its own fan
b. one fan supplies air to all furnaces
c. the fan is located in the uptake
d. none of the above
b. one fan supplies air to all furnaces
79
In the closed fire room system
a. each boiler has its own fan
b. each furnace has its own fan
c. the fan is located in the uptake
d. the fire room is supplied with air from one fan
d. the fire room is supplied with air from one fan
80
The air cock on a boiler is located at the
a. end of the superheater
b. highest point of the steam and the water drum
c. superheater inlet
d. top of the return headers
b. highest point of the steam and the water drum
81
Soot blowers should be used in proper sequence so that
a. excess stresses will not set up in the boiler
b. the deck will not be covered with soot
c. the soot will be swept toward the uptakes
d. there will not be a loss of steam pressure
c. the soot will be swept toward the uptakes
82
What is the first thing you would check on taking over a watch?
a. the bilges
b. the periscope
c. the water level
d. the oil pressure
c. the water level
83
The boiler with its fan(blower) located in the uptake is operating on
a. induced draft
b. forced draft
c. natural draft
d. none of the above
a. induced draft
84
A fire room that is completely isolated(closed) operates
a. induced draft
b. forced draft
c. natural draft
d. none of the above
b. forced draft
85
How many feedwater lines are connected to the boiler?
a. one
b. two
c. three
d. four
b. two
86
If the water in the gage glass has not been blown down for a period of time
the level of the water in the glass will be
a. the same as that in the steam and the water drum
b. less than that in the steam and water drum
c. more than that in the steam and water drum
d. none of the above
87
On taking over a watch
the fireman should check
a. the water level in the boilers
b. the bilges
c. the periscope
d. all of the above
88
When you are cleaning fuel-oil burner tips
use a
a. steel scraper
b. wire brush
c. brass knife
d. pocket knife
89
What is the amount of liquid in a tank if you get an ullage sounding of 11'4" and the empty ullage sounding of the tank is 32'2"?
a. 20'8"
b. 20'10"
c. 21'8"
d. 21'10"
b. 20'10
90
The amount of steam generated by a boiler is dependent upon
a. the size of the sprayer plate
b. the oil pressure
c. the air pressure
d. all of the above
d. all of the above
91
When installing a new gage glass in a water gage you should secure the bolts from
a. top of bottom
b. bottom of top
c. center
alternately
92
One of the main purposes of refractories in a boiler furnace is to
a. help preheat the air for the furnaces
b. help preheat the feedwater
c. protect economizer from excessive heat
d. prevent excessive furnace heat losses
d. prevent excessive furnace heat losses
93
All fuel-oil tanks are vented through
a. check vent to the settling tanks
b. gooseneck vent located on the main deck
c. check valve to the transfer pump
d. gooseneck vent which discharges to the settlers
b. gooseneck vent located on the main deck
94
All fuel-oil service pump steam valves are fitted with
a. safety locks
b. automatic controls
c. reach rods leading to a location outside the fire room
d. reach rods leading to the engine room
c. reach rods leading to a location outside the fire room
95
Which of the following fire extinguishers would not be found in the fire room?
a. foam type
b. sand
c. CO₂
d. SO₂
d. SO₂
96
What isthe average fuel-oil temperature range of the oil in the discharge line to the burners
a. 180⁰ - 200⁰
b. 150⁰ - 180⁰
c. 200⁰ - 220⁰
d. 150⁰ - 200⁰
a. 180⁰ - 200⁰
97
Which of the following is a common type of oil burners?
a. Bethlehem
b. Todd
c. B&W
d. all of the above
d. all of the above
98
The boiler gage glasses should be blown down
a. once a day
b. at the beginning of every watch
c. every 12 hours
d. every 8 hours
b. at the beginning of every watch
99
Gage pressure of 200 lbs per square inch is equivalent to what absolute pressure?
a. 215
b. 200
c. 185
d. 300
a. 215