1The component that absorbs heat into the refrigerant is the
a. metering device
b. condenser
c. compressor
d. evaporation
d. evaporation
2A high load affects the operation of a constant pressure expansion valve by
a. causing overload
b. requiring an external equalizer
c. starving the evaporator
d. all if the above
c. starving the evaporator
3The high side of the system includes
a. metering devices
b. an evaporator
c. a suction line
d. a receiver
a. metering devices
4Of the following
which component is found in a direct expansion valve system?
a. float valve
b. needle valve
c. globe valve
d. gate valve
5Superheat is heat added
a. with the aid of the automatic expansion valve
b. after all liquid has been changed to vapor
c. for the vaporization of the evaporator
d. to increase the heat of a substance
b. after all liquid has been changed to vapor
6An expansion valve is built most nearly like
a. a shut-off valve
b. a pressure-reducing valve
c. a blow-off valve
d. a diuble-seated globe valve
b. a pressure-reducing valve
7The low side of the system includes
a. a receiver
b. a compressor
c. a discharge
d. an evaporator
d. an evaporator
8What causes the drop in temperature and pressure as liquid refrigerant passes through the expansion valve
a. the superheat of the refrigerant
b. the change in the rate of flow of the refrigerant
c. the partial evaporation of refrigerant as it passes through the valve
d. the temperature and pressure of the refrigerant in the liquid line
c. the partial evaporation of refrigerant as it passes through the valve
9The heat used to change a liquid to a gas or vapor is called latent heat of
a. vaporization
b. fusion
c. condensation
d. superheat
a. vaporization
10The subcooling effect of a liquid refrigerant just before the expansion valve would result in
a. increased refrigerant effect
b. increased refrigerant density
c. increased miscibility of the oil
d. none of the above
a. increased refrigerant effect
11A thermometer is said to detect
a. heat of vaporization
b. sensible heat
c. potential energy
d. hidden heat
b. sensible heat
12The automatic expansion vakve maintains constant pressure at
a. the condenser inlet
b. the evaporator inlet
c. the liquid line
d. the condenser outlet
b. the evaporator inlet
13Hidden heat in refrigeration work is called
a. superheat
b. kinetic heat
c. sensible heat
d. latent heat
d. latent heat
14Which if the following is also referred to as a backward opersting valve?
a. thermal expansion valve
b. hand expansion valve
c. low side float
d. automatic expansion valve
d. automatic expansion valve
15What is another word for latent heat?
a. hidden heat
b. absolute heat
c. sensible heat
f. specific heat
a. hidden heat
16What controls the operation of a high-side float?
a. accumulator
b. evaporator
c. condenser and receiver
d. evaporator and condenser
c. condenser and receiver
17Heat added to a gas above the saturation temperature is called
a. specific heat
b. potential energy
c. superheat
d. all of the above
c. superheat
18In a high-side float
frost on the suction line indicates
a. recharging the refrigerant is necessary
b. an excessive amount of refrigerant is in the system
c. non-condensibles are in the system
d. there is a leak in the system
19The latent heat used to change a liquid to a gas or vapor is called the latent heat of
a. condensation
b. fusion
c. evaporization
d. temperature
c. evaporization
20On a refrigeration system with a high-side float metering device
what happens if the float fills with liquid refrigerant and sinks?
a. the evaporator starves
b. the evaporator floods
c. the compressor stalls
d. the condenser starves
21Convection is the process by which
a. heat moves through gases and liquids
b. transfer of heat occurs by direct contact
c. heat gives up to the surrounding air
d. heat changes state
a. heat moves through gases and liquids
22In a flooded evaporator using an accumulator and float valve
flash gas
a. passes directly into the evaporator
b. passes directly into the suction line
c. does not occur
d. stays in the receiver
23Conduction is the transfer of
a. heat by means of movement
b. heat by direct contact between two objects
c. heat by means of radiation of the sum
d. molecules in motion around a substance
b. heat by direct contact between two objects
24A flooded system with a low-side float uses a thermostat
which controls the liquid line solenoid valve. The thermostat is satisfied and the room continues to cool due to
a. a drop in head pressure
b. the pumping out of low side
c. all of the above
d. none of the above
25Saturated vapor is
a. heat that can be sensed
b. the number of Btu required to change the state of an object
c. a substance that has just turned into a vapor
d. all of the above
c. a substance that has just turned into a vapor
26One advantage of a low-side float system is that it
a. requires a large amount of refrigerant
b. can be used with a water cooled condenser
c. eliminates flash gas in the evaporator
d. can be used with a low starting torque motor
c. eliminates flash gas in the evaporator
27The evaporator absorbs heat from the air or brine because the liquid refrigerant entering the evaporator
a. has a lower temperature than the air or brine
b. has a higher temperature than the air or brine
c. boils to a low-pressure gas
d. bouls to high-pressure gas
b. has a higher temperature than the air or brine
28One disadvantage of a low-side float system is that it
a. is nonadjustable
b. requires a large amount of refeigerant
c. is very expensive
d. cannot be used on multiple systems
b. requires a large amount of refeigerant
29The evaporator
a. removes heat from the refrigerant
b. absorbs heat into the refrigerant
c. stores heat into the refrigerant
d. keeps the compressor busy
b. absorbs heat into the refrigerant
30In a flooded system
a low-side float is used as a metering device
31As the load on an evaporator decreases
a. the discharge pressure increases
b. the oil pressure increases
c. the suction pressure increases
d. the suction pressure decreases
d. the suction pressure decreases
32Flash gas forms in the
a. compressor
b. condenser
c. evaporator
d. heat exchanger
c. evaporator
33The heat picked up in the evaporator must equal
a. the heat gained by the condenser
b. the heat lost by the condenser
c. the heat of compression
d. the heat lost by the medium being cooled
d. the heat lost by the medium being cooled
34The flash gas loss at the expansion valve is approximately
a. 2%
b. 5%
c. 22%
d. 12%
d. 12%
35The disadvantage of a flooded system is
a. it cannot be used on multiple systems
b. it needs a large charge of refrigerant
c. it cannot be used with a low-pressure motor control
d. it can be used only with ammonia
b. it needs a large charge of refrigerant
36What does a high superheat mean?
a. flooded evaporator
b. starved evaporator
c. pressure evaporator
d. motor speed too high
b. starved evaporator
37Flooded feeds are diferent from direct expansion feeds because they
a. allow for regurgitation of liquid refrigerant
b. use bigger and better evaporators for this purpose
c. are not as effective in operation
d. allow for recirculation of liquid refrigerant
d. allow for recirculation of liquid refrigerant
38What does a low superheat indicate?
a. flooded evaporator
b. starved evaporator
c. pressure evaporator
d. motor speed too low
a. flooded evaporator
39The suction pressure of any refrigerant system is adjusted
a. to a corresponding evaporator temperature below the material being cooled
b. to a corresponding evaporator temperature equal to the material being cooled
c. to a pressure above atmospheric at all times
d. none of the above
a. to a corresponding evaporator temperature below the material being cooled
40Which of the following distributors are not used with an external equalizer thermostatic expansion valve
a. manifold type
b. venturi type
c. centrifugal type
d. pressure-drop type
a. manifold type
41A direct expansion evaporator has frost on the upper and lower coils.
This indicates
a. the evaporator is flooded
b. the evaporator is starved
c. the evaporator is short of refrigerant
d. there is coil logging in the evaporator
d. there is coil logging in the evaporator
42Thermal expansion valves are generally at stated suction temperature in
a. tons of refrigeration effect
b. pounds per minute of refrigerant pumped
c. pounds per hour of refrigerant pumped
d. cubic feet per minute of refrigerant pumped
a. tons of refrigeration effect
43When the evaporator load increases
what happens to the suction pressure?
a. it decreases
b. it increases
c. it stays the same
d. none of the above
44On an operating electric expansion valve
if the thermistor senses superheat on the suction line
45Baffles in a gravity coil evaporator are used
a. for condensation
b. for proper air flow
c. to prevent moisture carry-over
d. all of the above
d. all of the above
46The purpose of a condenser is to
a. remove water from the refrigeration system
b. add heat to the refrigeration system
c. remove heat from the refrigeration
d. store liquid refrigeration
c. remove heat from the refrigeration
47The temperature of the medium being cooled must be
a. below the freezing point of the area to be cooled
b. above the evaporator temperature
c. equal to the evaporator temperature
d. below the evaporator temperature
b. above the evaporator temperature
48An atmospheric condenser is generally
a. on the floor under the roof
b. in the refrigeration room
c. on the roof
d. none of the above
c. on the roof
49Assuming all other conditions are constant
a. as low-side pressure falls
compressor capacity increases
b. as load decreases
50A condenser is
a. a good cost-saving accessory to a refrigeration system
b. the exit for heat in a refrigeration system
c. always mounted above the compressor
d. always mounted below the compressor
b. the exit for heat in a refrigeration system
51The two basic types of evaporators are
a. prime surface and finned
b. finned and plate
c. direct expansion feed and plate
d. flooded and direct expansion feed
d. flooded and direct expansion feed
52If a refrigerating system does not react to an adjustment of the TXV
it may due to
a. non-condensable gases in the system
b. insufficient condenser water flow
c. an oil-clogged coil or evaporator
d. excessive motor speed
53A decrease in load on an evaporator cause
a. more refrigerant to be required
b. pressure drop in the evaporator
c. increase in evaporator capacity
d. more heat to be absorbed
b. pressure drop in the evaporator
54In a compression refrigeration system
if the capillary line on the remote bulb of the TXV breaks and the charge is lost
55closes
d. first closes
then opens
57Which of the following statement is most nearly correct?
a. The efficiency of an evaporator coil decreases as the frost thickness increases
b. The efficiency of an absorber depends on and varies directly with the compressor speed
c. To lubricate the inside surfaces of an evaporator coil
10 drops of machine oil per minute should be pumped into the coil
d. To lubricate the cylinder walls of an ammonia compressor
58Thermostatic expansion valves are rated in
a. superheat settings
b. horsepower
c. tons of refrigeration
d. all of the above
c. tons of refrigeration
59Prime surface evaporators operating below 32⁰F must frequently be
a. purged
b. cleared
c. defrosted
d. painted
c. defrosted
60TXV ratings are based on
a. slightly sub-cooled liquid entering the valve
b. vapor-free bulb of a TXV valve were moved to the valve
c. liquid with a small amount of vapor were moved to the valve
d. 10⁰F sub-cooled liquid entering the valve
b. vapor-free bulb of a TXV valve were moved to the valve
61Which of the following would not cause a starved evaporator?
a. improper bulb location
b. clogged distributor line
c. shortage of refrigerant
d. metering device stuck in open position
d. metering device stuck in open position
62If the feeler bulb of a TVX valve were moved to the
a. more than 10 superheat
b. less than 10 superheat
c. no effect on superheat
d. fluctuating superheat
a. more than 10 superheat
63A Freon-12 refrigerating system in an air conditioning plant is equipped with a finned-tube evaporator. In operation
the outer surface of this evaporator is wet. Thus the evaporator is
a. not operating at highest efficiency
b. not receiving enough efficiency
c. operating efficiency
d. operating with an oversized expansion valve
64An external equalizer is used on an evaporator with a pressure drop of
a. less than 2 pounds
b. more than 2 pounds
c. less than 10 pounds
d. more than 10 pounds
b. more than 2 pounds
65The fastest way to remove frost from a direct expansion finned-tube evaporator is
a. shut it down and let the frost melt
b. run a hot gas line to the coil
c. wash frost off with warm water
d. escape frost off
b. run a hot gas line to the coil
66A thermostatic expansion valve with a static setting of 7 superheat would have a field setting of
a. 7 superheat
b. 0 suerheat
c. 4 superheat
d. 11 F superheat
d. 11 F superheat
67A predetermined amount of refrigerant is used in what type of evaporator?
a. flooded evaporator
b. direct-expansion evaporator
c. indirect-type chiller
d. plate-type evaporator
b. direct-expansion evaporator
68If the bulb of a TXV is installed right after the expansion valve
it is installed
a. correctly
b. incorrectly
c. in accordance with manufacture's requirements
d. as an optional choice
69The selection of the proper evaporator depends mainly on
a. price
b. size
c. color
d. application
d. application
70If you open the adjustment of a TVX
you
a. raise the suction pressure
b. lower the suction pressure
c. raise the superheat
d. lower the superheat
71What happens in an evaporator?
a. high-pressure liquid converts to low pressure liquid
b. refrigerant in the gas state is saturated
c. low-pressure gas converts to low pressure liquid
d. high-pressure gas converts to low pressure liquid
c. low-pressure gas converts to low pressure liquid
72A thermostatic expansion valve was factory set at 0 superheat. How much was the field setting?
a. 0-3
b. 3-5
c. 4-8
d. 10-15
c. 4-8
73Is the temperature outside the evaporator higher or lower than the inside temperature?
a. higher
b. stay the same
c. lower
d. 10 dehrees lower
a. higher
74a TEV is attached to a fined evaporator coil with the bulb clamped to the suction line. In normal operation
the suction gas will leave this coil most nearly in the state of
a. 0-5 superheat
b. 7-10 superheat
c. 10-15 superheat
d. 15-20 superheat
75Secondary refrigerants are usually
a. a zeotrope
b. halocarbons
c. water or brine
d. triflouromethane
c. water or brine
76A direct expansion cooling coil has a TXV. If the load variations are wide and subject to rapid change
the valve should be set for superheat from
a. 1-3 F
b. 3-5 F
c. 7-9 F
d. 10-15 F
77In a refrigerant system
where would you find superheat?
a. after the metering device as refrigerant enters the evaporator
b. in the middle of the evaporator coil
78In a refrigeration system
the bulb of the TEV is clamped in the middle of the evaporator coil. When operative the probability is that
a. the vapor boiled off will be 100% saturated
b. the superheat in the evaporator will decrease
c. the superheat in the evaporator will increase
d. the liquid leaving the TEV will be hot
79The direct expansion system
compared to the flooded system
80A TEV shipped from the factory has static superheat setting of
a. 3 F
b. 5 F
c. 7 F
d. 10 F
c. 7 F
81The refrigerant leaving a flooded evaporator is
a. just like that leaving a D-X evaporator
saturated slightly superheated
b. just like that leaving a D-X evaporator
82The static setting of a TXV is set
a. in the factory
b by the operator
c. in the field
d. all of the above
a. in the factory
83The flow of refrigerant into a flooded evaporator is controlled so it has
a. mostly liquid refrigerant at the inlet but gas near the outlet
b. all its tubes wetted by liquid refrigerant from beginning to end
c. mostly liquid refrigerant at its outlet but gas at its inlet
d. a mixture of liquid and vapor refrigerant in its tubes from beginning to end
b. all its tubes wetted by liquid refrigerant from beginning to end
84What is the purpose of an external equalizer on a TEV?
a. It lubricates the coil of the TEV
b. It equalizes the pressure in the evaporator
c. to eliminate the effect of the pressure drop across the evaporator
d. none of the above
c. to eliminate the effect of the pressure drop across the evaporator
85As flash gas increases
evaporator capacity
a. increases
b. decreases
c. stay the same
d. increases or decreases depending on the evaporator pressure
86Assume a TXV is set for 10 superheat. This means the gas passing yhe remote bulb is about 10
a. above the temperature of the evaporating refrigerant
b. below the temperature of the evaporating refrigerant
c. above the temperature of the ambient air temperature
d. below the temperature of the ambient air temperature
a. above the temperature of the evaporating refrigerant
87Superheat is wanted at the outlet of a D-X evaporator mainly to
a. improve evaporator efficiency
b. increase evaporator capacity
c. protect the compressor
d. increase system capacity
c. protect the compressor
88In a particular air conditioning system using R-12
a refrigerant distributor is not necessary. In this case a TXV with an external equalizer should be used when the pressure drop through the evaporator is
a. .5 psi
b. 1.00 psi
c. 1.5 psi
d. 2.5 psi
89An evaporator that fails to provide superheat at its outlet places which compressor is in the most serious danger?
a. rotary
b. centrifugal
c. reciprocating
d. screw
c. reciprocating
90A thermostatic expansion valve in a refrigeration system
a. regulates the pressure in the evaporator
b. regulates the compressor pressure
c. regulates the flow of refrigerant to the pre-cooler
d. modulates and controls the flow of refrigerant to the evaporator
d. modulates and controls the flow of refrigerant to the evaporator
91A prime-surface evaporator is one that
a. has prime sprayed on it to protect it
b. is either a plate-surface or plate-finned type
c. is either a bare-tube or plate-surface type
d. none of these
c. is either a bare-tube or plate-surface type
92If the external equalizer line of a TXV is disconnected from the evaporator
the following might result
a. no refrigeration
b. excess refrigeration
c. A or D
d. higher suction pressure
93Scale from water deposits wil build up and need to be removed periodically from
a. the outside and inside of the tubes of a D-X cooler
b. the inside and outside of the tubes of a flooded cooler
c. the inside of a tube-and-shell cooler only
d. the outside of a tube-and-shell cooler only
c. the inside of a tube-and-shell cooler only
94What is the highest pressure tjat can be exerted on a Freon system's TXV bukb (vapor charge)
with a saturated temperature of 60
95What is the difference between flooded and dry-expansion shell and tube evaporators?
a. The flooded cooler has refrigerant in the shell and water in the tubes
b. The dry-expansion evaporator has refrigerant in the tubes and brine in the shell
c. The flooded cooler has refrigerant in the tubes and brine in the shell
d. A or B
d. A or B
96When using a TXV in a Freon system eith the temperature range of +40 to -40
what type of charge would you use in a remote bulb?
a. gas charge
b. gas cross charge
c. liquid charge
d. liquid cross charge
97The TXV is controlled by
a. coil temperature
b. the difference between gas temperature and the temperature corresponding to the gas pressure
c. the difference between gas pressure and the pressure corresponding to the gas temperature
d. coil pressure
b. the difference between gas temperature and the temperature corresponding to the gas pressure
98Superheat is heat added
a. in changing liquid vapor
b. in raising temperature of water
c. after all liquid has been changed to vapor
d. to increase pressure
c. after all liquid has been changed to vapor
99The feeler bulb of a TXV is located
a. before the evaporator
b. after the evaporator
c. midway along the evaporator
d. on the suction line next to the compressor
b. after the evaporator
100An automatic expansion valve system on variable loads causes
a. a flooded evaporator on high loads
b. no apparent change in operation
c. an overloading of the compressor motor
d. a starved evaporator at high loads
d. a starved evaporator at high loads
101The TXV valve has three operating pressures
a. evaporator pressure
spring suction pressure
b. evaporator pressure
102One main disadvantage of an automatic expansion valve is that it
a. requires a critical charge of refrigerant
b. is only used on domestic refrigerators
c. cannot adapt to variable loads
d. all of the above
c. cannot adapt to variable loads