1A refrigerating unit of one ton capacity can remove:
a. 500 Btu per min
b. 288 Btu per min
c. 200 Btu per min
d. 100 Btu per min
c. 200 Btu per min
2Too much oil in the compressor would
a. absorb too much refrigerant from the system
b. damage the expansion valve
c. cause leakage through the shaft seals
d. deposit oil on the condenser tubes
a. absorb too much refrigerant from the system
3The refrigerant with the lowest boiling point is:
a. NH₃
b. CO₂
c. F-12
d. F-22
b. CO₂
4A ton of refrigeration is equal to the removal of:
a. 288
000 Btu per 24 hrs
b. 28
5Which of the following would cause a high suction pressure?
a. expansion valve not open wide enough
b. expansion valve open too wide
c. king valve not open wide enough
d. dirty dehydrator
b. expansion valve open too wide
6Which of the following would cause high head pressure?
a. dirty condenser
b. insufficient cooling tower
c. air in the cooling tower
d. all of the above
d. all of the above
7Which of the following would cause low head pressure?
a. too much cooling tower
b. insufficient refrigeration gas
c. insufficient cooling water
d. A and B
d. A and B
8The principle of the mechanical refrigeration is
a. the absorption of temperature under heat
pressure
9The function of the expansion valve is to
a. change the high pressure liquid to low pressure liquid
b. regulate the amount of liquid refrigerant to expansion coils
c. change the gas refrigerants to a liquid
d. shut off the flow of refrigerant to the condenser
b. regulate the amount of liquid refrigerant to expansion coils
10The oil separator (trap) is located between the
a. compressor discharge valve and the condenser
b. condenser and the receiver
c. receiver and the king valve
d. receiver and the expansion valve
a. compressor discharge valve and the condenser
11The purpose of the oil trap is
a. to remove oil from the charging tank
b. to add oil to the compressor
c. to remove oil from the refrigerating gas
d. none of the above
c. to remove oil from the refrigerating gas
12The boiling point of ammonia at atmospheric pressure is
a. -28⁰C
b. +28⁰C
c. +28⁰C
d. -28⁰F
d. -28⁰F
13The boiling point of CO₂ at atmospheric pressure is
a. +10⁰F
b. -110⁰C
c. +110⁰C
d. -110⁰C
b. -110⁰C
14The boiling point of Freon at atmospheric pressure is
a. -22⁰F
b. +22⁰F
c. +32⁰F
d. -32⁰F
a. -22⁰F
15The dehydrator is located between the:
a. receiver and the king valve
b. receiver and the expansion valve
c. condenser and the king valve
d. condenser and receiver
b. receiver and the expansion valve
16The purpose of the dehydrator is to
a. remove oil from the refrigerant
b. add more refrigerant to the system
c. remove moisture from the refrigerant
d. remove moisture from the crankcase oil
c. remove moisture from the refrigerant
17Which of the following would you apply if a person got Freon in his eyes?
a. soapy water
b. sterile mineral oil
c. clean water
d. sodium bicarbonate
b. sterile mineral oil
18The thermal expansion valve
a. controls the amount of gas coming from the dehydrator
b. maintains a constant superheat of the gas leaving the evaporator coils
c. controls the amount of gas going to the receiver
d. removes trap oil from the refrigerant
b. maintains a constant superheat of the gas leaving the evaporator coils
19Water in the refrigerant is liable to
a. freeze on the expansion seat and cut the flow of liquid refrigerant
b. emulsify the oil in the compressor
c. freeze in the king valve
d. clog the oil trap
a. freeze on the expansion seat and cut the flow of liquid refrigerant
20The purpose of the scale trap is to:
a. control the amount of scale going to the compressor
b. remove insoluble gases from the refrigerant
c. remove dirt
scale and metal chips from the refrigerant
d. dissolve scale and dirt in the system
21A double seated valve allows the valve to be:
a. packed only in the closed position
b. packed in wide open or closed position
c. operated as a suction or discharge valve
d. removed for replacement without shutting down
b. packed in wide open or closed position
22Sensible heat
a. can be measured with a thermometer
b. cannot be measured with a thermometer
c. changes in the receiver tank
d. increases with the cold
a. can be measured with a thermometer
23The latent heat of fusion is the amount of heat required to convert
a. two lbs of ice at 32⁰F to one lb of ice at 32⁰F
b. one lb of ice at 32⁰F to one lb of water 32⁰F
c. one lb of ice at 32⁰F to one lb of steam 32⁰F
d. two lbs of ice at 32⁰F to one lb water at 32⁰F
b. one lb of ice at 32⁰F to one lb of water 32⁰F
24The latent heat of vaporization of water is
a. 144 Btu
b. 940 Btu
c. 970 Btu
d. 288 Btu
c. 970 Btu
25The latent heat of vaporization is the amount of heat required to convert
a. one lb of water at 212⁰F to one lb steam at 212⁰F
b. one lb of water at 180⁰F to one lb of steam at 180⁰F
c. two lbs of water at 212⁰F to one lb of steam at 212⁰F
d. one lb of ice at 32⁰F to one lb of steam at 212⁰F
a. one lb of water at 212⁰F to one lb steam at 212⁰F
26Too high suction pressure could be caused by
a. expansion valve open too wide
b. leaky suction valves
c. expansion valve bulb not working properly
d. any of the above
d. any of the above
27How is an ammonia system purged so that the operator will not be overcome by the fumes?
a. into that atmospheric line
b. into a bucket of water
c. into a bucket of lube oil
d. back into compressor
b. into a bucket of water
28How is CO₂ system purged?
a. when CO₂ comes out
frost will form on a piece of metal held near the outlet
b. through the king valve
c. the CO₂ will come out in liquid form
d. pumped out with a suction pump
29How is Freon system purged?
a. the same as the ammonia system
b. the same as the CO₂ system
c. back to the extra supply bottle
d. with a reefer pump
b. the same as the CO₂ system
30The solenoid valve is
a. 144 Btu
b. 288 Btu
c. 940 Btu
d. 500 Btu
c. 940 Btu
31Where should you charge less than 6 pounds of refrigerant into a system?
a. any point downstream of the liquid line
b. on the low side of the system
c. on the high side of the system
d. the discharge service valve
b. on the low side of the system
32Latent heat
a. can be measured with a thermometer
b. can be measured with a pyrometer
c. cannot be measured with a thermometer
d. changes as the refrigerant cools
c. cannot be measured with a thermometer
33Absolute zero is
a. 970⁰ below zero on the Fahrenheit scale
b. 460⁰ below zero on the Farenheit scale
c. 144⁰ below zero on the Farenheit scale
d. the same as zero on the Centigrade scale
b. 460⁰ below zero on the Farenheit scale
34When the evaporator coils are located in the ice box
the system is known as a
a. direct system
b. low pressure system
c. indirect system
d. high-pressure system
35The amount of CO₂ or Freon in a cylinder is measured by
a. pressure
b. volume
c. weight
d. psi
c. weight
36The solenoid valve is controlled by
a. the amount of liquid in the system
b. the amount of gas in the system
c. the temperature in the condenser
d. the thermal switch operated by the icebox temperature
d. the thermal switch operated by the icebox temperature
37The purged valve is located
a. in the lowest part of the system
b. in the highest part of the system
c. on the receiver discharge
d. on the evaporator coils
b. in the highest part of the system
38The system should be purged
a. while the system is operating
b. while starting up the system
c. after the system has been shutdown for a few hours
d. once a week
c. after the system has been shutdown for a few hours
39The function of the compressor is to
a. pull the refrigerant gas through the system
b. increase the pressure of the refrigerant
c. discharge the refrigerant to the condenser
d. all of the above
d. all of the above
40The expansion valve is located between the
a. receiver and evaporator
b. evaporator and compressor
c. compressor and condenser
d. condenser and receiver
a. receiver and evaporator
41If frost forms on the cylinders
the cause would be
a. expansion valve not open wide enough
b. charging valve left open
c. expansion valve open too wide
d. dehydrator not working properly
42Which of the following would cause a high head pressure?
a. icebox door left open
b. insufficient cooling water
c. too much cooling water
d. suction valve not open enough
b. insufficient cooling water
43The high pressure side of the system is sometimes refered to as the
a. suction side
b. cold side
c. hot side
d. filling side
c. hot side
44A ton of refrigeration is equal to the cooling effect of
a. 2000 lbs of ice melting in 24 hrs
b. 2000 lbs of ice melting in 12 hrs
c. 2000 lbs of ice melting in 24 hrs
d. 2240 lbs of ice melting in 24 hrs
a. 2000 lbs of ice melting in 24 hrs
45The scale trap (liquid strainer) is located between the
a. compressor and oul separator
b. king(liquid) valve and expansion valve
c. expansion valve and evaporator coils
d. evaporator coils and compressor
b. king(liquid) valve and expansion valve
46When there is Freon leak
the halide torch will burn
a. orange
b. blue
c. white
d. green
47Which of the following could be used to check a leak in an ammonia system?
a. litmus paper
b. halide torch
c. sulphur stick
d. A and C
d. A and C
48Valves and piping in an ammonia system are made of
a. iron
b. brass
c. copper
d. bronze
a. iron
49In an ammonia system
the oul gage must be kept
a. closed except when checking oil level
b. open at all times
c. closed when machine is shut down
d. open when machine is shut down
50Freon is
a. colorless
b. odorless
c. nonpoisonous
d. all of the above
d. all of the above
51Which of the following gasket materials should be used on a Freon system?
a. metallic
b. asbestos
c. rubber
d. A and B
d. A and B
52A double-pipe condenser has
a. two piping system side by side
one with cooling water and one with refrigerant
b. a small pipe inside a larger pipe
53Air can be prevented from getting into the system by
a. keeping all glands and stuffing boxes on the high-pressure side tight
b. keeping the dehydrator clean at all times
c. keeping all glands and stuffing boxes on the low-pressure side tight
d. running the refrigerant through the aerator
c. keeping all glands and stuffing boxes on the low-pressure side tight
54The agent used in an indirect refer system is
a. sodium chloride
b. potassium chloride
c. calcium chloride
d. A and C
d. A and C
55An ammonia leak will turn litmus paper
a. blue
b. red
c. green
d. yellow
a. blue
56A sulphur stick burning in the presence of ammonia will give off a
a. dense yellow smoke
b. dense white smoke
c. dense red smoke
d. dense green smoke
b. dense white smoke
57If the compressor were to run continuously without lowering the temperature
the trouble would probably be
a. insufficient refrigerant in the system
b. leaks
c. leaky discharge valves
d. any of the above
58Ammonia leaks in the condenser can be detected by
a. smelling the discharge water
b. applying litmus paper to the circulating water discharge
c. adding water to peppermint to the system and tracing the smell
d. applying a soapy mixture to the condenser heads and looking for bubbles
b. applying litmus paper to the circulating water discharge
59When purging an ammonia condenser into a bucket of water
one can tell when the air is out and ammonia starts to come through by the
a. smell of ammonia being liberated from the water
b. color of the water turning green
c. color ofbthe water turning bluish
d. change of the bubbling sound of air to the crackling sound of ammonia
60Large leaks in a Freon system cannot always be detected with a halide torch because it changes color with slight test amount of Freon present. A large leak can be detected easier by applying
a. sheets of litmus paper to all joints and watch for color change
b. a soup suds solution
mixed with a little glycerin to hold the solution together
61When the evaporator coils are located in a brine solution and the brine is pumped through the ice box
the system is known as
a. a direct system
b. an indirect system
c. a low pressure system
d. a double-evaporator system
62Obstruction of the expansion valve is usually caused by
a. congealed oil in the system
b. scale
c. water in the system
d. all of the above
d. all of the above
63Too low suction pressure could be caused by
a. dirty scale traps
b. shortage of refrigerant gas
c. too much oil in the system
d. any of the above
b. shortage of refrigerant gas
64If an electrically operated compressor failed to start
the cause might be
a. an open switch
b. a blown fuse
c. burned-out holding coils in solenoid valve
d. any of the above
65The oil separator is located between the
a. evaporator and compressor
b. compressor and condenser
c. condenser and dehydrator
d. solenoid valve and the thermal expansion valve
b. compressor and condenser
66To help person who have been exposed to ammonia gas
one would
a. apply artificial respiration
b. wrap in warm blankets
c. apply cold compresses
d. douse with cold water
67If the compressor short cycles on the low pressure cut-out
the trouble might be
a. lack of refrigerant
b. dirty trap and strainers
c. too much frost on coils
d. any of the above
68Ammonia will corrode
a. copper
b. bronze
c. brass
d. all of the above
d. all of the above
69The dehydrating agent in the Freon system is usually
a. slaked lime
b. sodium chloride
c. activated alumina
d. calcium chloride
c. activated alumina
70If any of the electrically controlled devices in a Freon system malfunction
which of the following valves will also automatically shut-off?
a. king valve
b. expansion valve
c. solenoid valve
d. condenser cooling-water inlet valve
71Many pressure gages on a Freon system have two dials or graduations on one gage. The two dials represent
a. pressure and temperature
b. liquid pressure and gas pressure
c. suction and discharge pressure
d. cooling-water inlet and outlet temperatures
a. pressure and temperature
72A leaky discharge valve can usually be detected by
a. a fluctuating high-pressure gage
b. a drop in icebox temperature
c. a discharge pressure lower than normal
d. any of the above
d. any of the above
73The suction of a Freon should be
a. the pressure which corresponds with a temperature about 20F below the temperature of the ice box
b. the pressure which corresponds with a temperature of the icebox
c. the pressure which corresponds with a temperature about 20 above the temperature of the icebox
d. none of the above
a. the pressure which corresponds with a temperature about 20F below the temperature of the ice box
74The disadvantage of a CO₂ system over an ammonia system is the fact that:
a. the CO₂ system requires a larger prime mover
b. the CO₂ system operates at much higher pressure
c. the pipes and fittings of a CO₂ system must be of the high pressure type
d. all of the above
d. all of the above
75One disadvantage of a CO₂ system is the fact that
a. it is different to condense the refrigerant if the circulating water temperature is too high
b. it is difficult to condense the refrigerant if the circulating water temperature is too low
c. due to high pressure it is difficult to keep oil from mixing with refrigerant
d. it takes more refrigerant to keep the iceboxes cold
a. it is different to condense the refrigerant if the circulating water temperature is too high
76The crossover connection in an ammonia system can be used to
a. reduce the pressure on the discharge side of the condenser
b. hot-gas defrost
c. pump air out of the system
d. add refrigerant to the system
b. hot-gas defrost
77Another name for discharge pressure is
a. suction pressure
b. absolute pressure
c. head pressure
d. condenser pressure
c. head pressure
78Oil is used in the refrigerating system is
a. lube oil SAE 20
b. straight mineral oil
c. lube oil SAE 10
d. vegetable oil
b. straight mineral oil
79The discharge pressure on the compressor should be
a. the pressure which corresponds to a temperature from 5 to 15⁰F below that of the condenser discharge
b. the pressure which corresponds to a temperature from 5 to 15⁰F higher than the condenser discharge
c. the pressure which corresponds to a temperature equal of the condenser discharge
d. none of the above
b. the pressure which corresponds to a temperature from 5 to 15⁰F higher than the condenser discharge
80A leaky suction valve can usually be detected by
a. a fluctuating suction-pressure gage
b. a higher suction pressure
c. closing in on the suction valve having no effect on the suction pressure
d. any of the above
d. any of the above
81The purpose of relief valves on refrigerating machines is to
a. prevent overloading in the iceboxes
b. bypass the compressor when dehydrating
c. prevent excessive pressure in case of stoppage on the discharge side of the system
d. A and B
c. prevent excessive pressure in case of stoppage on the discharge side of the system
82The relief valve on an ammonia machine is located
a. on the discharge pipe from the condenser
b. on the discharge pipe from the compressor
c. in the compressor head
d. A or B
c. in the compressor head
83The relief valve on a CO₂ machine is located
a. on the discharge pipe from the condenser
b. next to the king valve
c. on the discharge pipe between the compressor and the discharge valve
d. in the compressor head
c. on the discharge pipe between the compressor and the discharge valve
84Excess frost on the evaporator coils
a. keeps the icebox cooler
b. reduces the efficiency of the plant
c. takes the load off the compressor
d. does not affect the system
b. reduces the efficiency of the plant
85Air circulation in the icebox is accomplished by the use of
a. louver doors
b. hollow sidewalls
c. diffuser fans
d. air vents to decks
c. diffuser fans
86Before securing a compressor to do maintenance on it
be sure to
a. pump down system
b. have spare parts ready
c. purge the system
d. A and B
87Some causes of a noisy compressor are
a. worn bearings
pins
88Slugging is usually caused by
a. too much oil in the system
b. too much refrigerant in the system
c. expansion valve not operating properly
d. too much cooling water to condenser
c. expansion valve not operating properly
89Zinc rods are found in the
a. evaporator coils
b. salt water side of condenser
c. compressor crankcase
d. refrigerant side of crankcase
b. salt water side of condenser
90A double-trunk piston is used to
a. prevent gas from gettinf to crankcase
b. absorb some of the side trust
c. prevent oil from mixing with the refrigerants
d. all of the above
d. all of the above
91The purpose of the receiver is to
a. cool the refrigerant gas
b. separate the oil from the refrigerant
c. store the refrigerant
d. condense the refrigerant
c. store the refrigerant
92When a pressure gage reads zero
the absolute pressure is
a. 30psi
b. 14.7 psi
c. 0 psi
d. 17.4 psi
93The heat used to change a solid to a liquid is called
a. latent heat of fusion
b. sensible heat fusion
c. latent heat of liquid
d. specific heat of fusion
a. latent heat of fusion
94The heat used to change a gas to a vapor is called
a. latent heat of fusion
b. latent heat of vaporization
c. specific heat of vaporization
d. latent heat of the gas
b. latent heat of vaporization
95Sweating of the crankcase is caused by
a. too much superheat
b. insufficient superheat
c. expansion valve hang up
d. too much oil in the system
d. too much oil in the system
96If an automatic Freon system will not start up
check the
a. high-pressure cutout
b. low-pressure cutout
c. reset mechanism
d. all of the above
97The cooling-water side of the condenser should be opened for inspection every
a. six months
b. year
c. two years
d. three months
d. three months
98If the thermal expansion vakve becomes inoperative the iceboxes will have to be controlled by the
a. solenoid valve
b. manual expansion valve
c. king valve
d. manual solenoid valve
b. manual expansion valve