3Rad/s to Hz
1 rad/s / 2pi = 1 Hz
4Equivalent Thickness
$t_{eq}=r_{2}ln(\frac{r_{2}}{r_{1}})$
5Energy Utilization Index (EUI)
${total~yearly~energy}/{building~area}$
6Cost Utilization Index (CUI)
${total~yearly~energy~cost}/{building~area}$
7Calculate Rate of Return
Equate two figures into the same time period (e.g. annual) and solve for interest rate by looking up value on interest tables
8Effect of building orientation on heat gain
Northern hemisphere:
south-facing: receive more sunlight in the winter
west-facing: receive more sunlight in afternoon during summer;
east-facing: receive more morning sunlight;
north facing: receive minimal sunlight year-round
9Mechanical horsepower (MHP)
power produced by pump/fan; amount of power required to meet needs of the system
10Brake horsepower (BHP)
power output of motor to turn on pump or fan; $BHP=\frac{MHP}{\eta_{mech}\%}$
11(Standard) motor horsepower
size of the motor
12Motor HP rating
standard size above BHP
13Electrical Power (P)
electrical input required to turn on the motor and overcome friction losses
14Real Power
Electricity that can do actual work
15Power Factor
Used to find real power; $S_{supplied~to~motor~(VA)}=\frac{P~[W]}{pf}$
16Electrical horsepower efficiency
$\frac{Brake~HP}{\eta_{motor}\%}=\frac{{Mechanical~HP}}{\eta_{motor}\%*\eta_{mech}\%}$
17Explain the vapor compression cycle
1. Evaporator: low pressure, low temp liquid/vapor mixture → absorbs heat → low pressure, high temp gas; 2. Compressor: low pressure, high temp gas → compressed high pressure, high temp gas; 3. Condenser: high pressure, high temp gas → high pressure, low temp liquid; 4: Expansion device: high pressure, low temp liquid → low pressure, low temp liquid/vapor mixture

18Vapor compression cycle steps
19Evaporator
warm air/water used to evaporate all liquid parts of mixture into saturated vapor; isobaric and ideally isothermal; cool water to chilled water that is distributed to air handlers
20Compressor
raises temperature of gas above temperature of fluid in condenser; ideally isentropic but some enthalpy change due to not being 100% efficient
21(Isentropic) Compressor efficiency
$Compresser~Efficiency~(\%)=\frac{h_{2,ideal}-h_{1}}{h_{2,actual}-h_{1}}$
22Condenser
cold air.water used to remove heat from gas and condense it to liquid; reject heat to a heat sink via air cooling (fans blow air over condenser) or water cooling (piping to cooling tower)
23Superheat
X degrees beyond the saturation temperature. Evaporator superheats gaseous refrigerant.
24Expansion device
reduces pressure of liquid adiabatically, where some is turned to gas
25EER
Energy efficiency ratio, measures practical efficiency of cycle; $EER=3.412*COP$
26IPLV
Integrated part load value; kW/ton metric given at various % load at standard AHRI conditions
27NPLV
Non-standard part load value; same as IPLV but adjusted to account for design (non-standard) conditions
28Absorption cycle
two shells, refrigerant (water) + absorber (lithium-bromide/ammonia), heat source (hot water/steam, typically used with waste heat)
29Absorption cycle COP
COP=evaporator energy (Btuh)/Heat in (Btuh), typically 1.5
30Isentropic
constant entropy; ideal compressors
31Adiabatic
constant enthalpy; heat does not enter/leave system; dehumidifiers, evaporative coolers, expansion valves, throttling valve
32Isothermal
constant temperature
33Isobaric
constant pressure
34Generic steam, refrigerant, and total heat equation
$Q=\dot{m}\Delta h$ or $q=mC_{p}\Delta T$
35Sensible heat ratio
$SHR=\frac{{Sensible~Heat}}{Total~Heat}$, i.e. slope of line on the protractor
36Heat of vaporization
$h_{gf}=h_{g}-h_{f}$; energy to vaporize liquid to gas
37Lever rule
$T_{mix,db}=T_{1,db}*\%_{1}+T_{2,db}*\%_{2}=\frac{{T_{1,db}*CFM_{1}+T_{2,db}*CFM_{2}}}{CFM_{1}+CFM_{2}}$
38What is the lever rule valid for?
Dry bulb temperature, humidity ratio, or enthalpy. NOT wet bulb temperature
39Dew point
Horizontally left from point until you hit saturation curve. NOT the same as wet bulb temperature.
40Horizontally right on psychrometric chart
sensible heating, decrease in RH; heating coils
41Horizontally left on psychrometric chart
sensible cooling, increase in RH; cooling coils
42Vertically up on psychrometric chart
latent heating, humidification; steam humidifier
43Vertically down on psychrometric chart
latent cooling, dehumidification
44Energy added from steam humidification
Use the slope obtained from the nomograph on the psych chart

45Chemical dehumidifier
downward diagonal movement depending on temperature of desiccant; possibly adiabatic
46Regeneration
Heating dessicant to retransfer moisture into air
47Lithium-Chloride
Can be sprayed with water solution over humid air to dehumidify; Li-Cl has high affinity for water
a) higher concentration of Li-Cl absorbs more moisture and vice versa
b) lower temperature can absorb more moisture and vice versa
48Evaporative cooling
Blow dry air over water or through water droplets
upward diagonal to left; essentially adiabatic since enthalpy lost be sensible cooling is gained by latent heating
49Altitude correction equation
in the handbook. only use DF or corrected air density, not both.
50Heat from steamflow
$Q_{steam}=\dot{m}*h_{fg}$
51Conductive heat transfer coefficient k units
per thickness, can be per inch $[\frac{Btu-in}{{hr*ft^2*^\circ}F}]$ or per ft $[\frac{Btu}{{hr*ft*^\circ}F}]$
52Resistance to heat transfer
the reciprocal of conductive heat transfer coefficient, k (includes thickness); $\frac{{hr*ft^2}*^{\circ}F}{Btu*in}$
53Resistance in series
sum of all resistances
54Resistance in parallel
reciprocal of all resistances summed
55Convective heat transfer coefficient
h, based on flow over surface; check handbook of h value of vertical, horizontal surfaces with/without wind
56Black body
most efficient at emitting radiation and absorbing incident energy; emissivity = absorptivity = 1
57$\alpha + \rho + \tau$
always equal to 1 for any type of body
58Identify heat gains and their forms of heat transfer
roof/walls: conduction/solar radiation
skylights/windows: conduction/solar radiation
ventilation/infiltration
lights
people
equipment
59Heating load sources
roofs/walls: conduction
skylights/windows: conduction
ventilation/infiltration
60Surface film coefficient
combined convective and radiative heat transfer coefficient for indoor and outdoor conditions to help find overall heat transfer coefficient; values in the handbook
61CLTD
Cooling Load Temperature Difference; used for heat transfer through roof and walls instead of change in temperature
Only used for cooling loads
62Heat gain from motors
depends on how the motor is configured relative to its respective equipment; equations in handbook

63Appliances/Kitchen equipment heat transfer
hooded appliances have only sensible heat load since all latent and convective loads removed; if hooded use radiation factor
64Surface temperature of pipes
$Convection~(T_{inside}-T_{surface})=Conduction~(T_{surface}-T_{ambient})$
65Apparatus dew point (ADP)
temperature at which all air would be cooled if the cooling coil was 100% effective. Must be on saturation curve
66Contact factor
how much of air hits and is cooled by coil, percentage of air cooled to apparatus dew point; $Contact~factor=1-Bypass~Factor$
67Bypass factor
percent of air not cooled to ADP, function of airflow; $Bypass~Factor=\frac{{h_{leaving~coil}-h_{ADP}}}{h_{entering~coil}-h_{ADP}}=\frac{{T_{leaving~coil}-T_{ADP}}}{T_{entering~coil}-T_{ADP}}=\frac{{W_{leaving~coil}-W_{ADP}}}{W_{entering~coil}-W_{ADP}}$
68Fitting losses
account for fitting losses using k as a loss factor (found in handbook)
69Steam quality
$x=\frac{{h-h_{f}}}{h_{g}-h_{f}}=\frac{m_{vapor}}{m_{vapor}+m_{liquid}}$ (in handbook)
70Explain how a cooling tower works
Transfers heat from water to air via evaporative cooling (via a small portion of liquid being evaporated by an airstream) to cool water. Air enters dry and leaves higher in temperature and near saturation while water is cooled down to a lower dry bulb temperature.; $q_{cold~water}=q_{air}$

71Approach
$Approach=T_{water,out}-T_{air,in,wb}$; describes performance of cooling tower, where the smaller the approach the closer to maximum possible heat transfer
72Range
$Range=T_{water,in}-T_{water,out}$;
73Effectiveness of cooling towers
$Effectiveness=\frac{Range}{Range+Approach}*100\%$
74Water loss and make-up of cooling tower
Equate water heat loss to heat gain through evaporation: $500*Q~[gpm]~*(T_{in}-T_{out})=500*evaporation~rate~\left[ \frac{gal}{min} \right]*H_{vp}~\left[ \frac{Btu}{lbm} \right]$
75Cooling tower - Drift
Amount of water carried out through airstream (~0.2%)
76Blow-down
Draining of concentrated TDS then replacement with fresh water
77Mechanical Cooling Tower
move air through cooling tower using mechanical fans
78Natural draft cooling tower
move air based on difference in buoyancy of airstream inside and outside of cooling tower
79Induced cooling tower
fans located at exit of airstream and suck air into cooling tower
80Forced draft cooling tower
Fans blow into the cooling tower and located at airstream entrance
81Counter-flow v Cross-flow
Counter-flow - air and water have directly opposing directions; cross-flow - air and water flow 90 degrees to each other
82Higher heating value
gross heat from combustion of fuel (Btu/lb or Btu/lb^3)
83Lower heating value
net heating value from combustion without latent heat of vaporization
84Energy from a boiler/furnace
$Q_{boiler}=\dot{m}_{fuel}*{HHV}*\eta_{boiler}$
85Condensing boiler
Extract additional heat from flue gases to provide higher efficiencies by condensing moisture out of waste stream to provide additional heating
86Firetube boiler
non-condensing; products of combustion contained within boiler tubes and water passed over tubes within a shell
87Watertube boiler
non-condensing; products of combustion within shell and water kept within small tubes
88Parallel vs Counterflow heat exchanger
Counterflow increases coil capacity and maximizes heat transfer
89NTU Method
Number of transfer units method; used for when LMTD unkown:
1. calculate NTU
2. Find effectiveness based on NTU and heat capacity ratio $C_{r}$,
3. Calculate heat transfer rate: $Q_{actual}=Q_{max}*\epsilon$, $Q_{max}=C_{min}*(T_{hot,in}-T_{cold,in})$
4. Solve for remaining unknowns using $Q=mc_{p}\Delta T$
90Absorption chiller
compressor is replaced with a generator/absorber and a heat source
91Chiller (compressor) types
Positive displacement:
Scroll - 10-400 tons
screw - 70-500 tons
rotary - 70-500 tons
reciprocal - 10-60 tons
Dynamic: centrifugal
92Positive displacement
compressing gas by squishing gas into an ever smaller volume
93Hermetic compressor
compressor and motor in a welded, airtight container; need to account for motor heat
94Open Drive
compressor and refrigerant located in an enclosure while motor connected outside via a shaft
95Semi-hermetic
motor and compressor located in a mechanically sealed container that can be opened
96Direct expansion (DX) system
refrigerant directly cools air
97Variable refrigerant flow (VRF)
direct expansion system; split between condensing unit (compressor, condenser, expansion valve) and fan coil unit (evaporator and fan) where refrigerant flow varies to maintain temperature
98Heat pump
Uses vapor compression cycle to heat instead of cool; condenser used to heat space and evaporator absorbs heat from exterior; heat source from ambient air, water, or ground
99Pump types
Double suction - fluid enters impeller on both sides
end suction - suction and discharge 90 degrees to each other
in-line - suction and discharge in-line
split-case - number of stages fluid proceeds through
centrifugal - conversion of rotational kinetic energy to produce a flow rate
100Fan types
Axial - fan shaft with fan blades attached around the shaft
Centrifugal - fan wheel with blades (impellers) along the circumference of the wheel. Air enters center where centrifugal force due to spinning of the fan wheel causes increase in air speed that creates a suction pressure at inlet of the fan wheel. Air then flows out the edges of the fan wheel and follows the fan housing to the air outlet
101Axial fan types
Propeller - propeller fan in housing
Tube-axial - propeller fan placed in tube; can handle higher pressure
Vane-axial - variation of tube-axial where inlet vanes provided to straighten air and increase efficiency
102Centrifugal fan types
forward inclined, backward incline, backward incline airfoil, propeller
103Pump curve
Unique to pump and given by manufacturer

104Pump System Curve
based on piping system (pipes, fittings, valves, and equipment) that the pump will be connected to; static pressure translates curve up

105Operation point of pump
intersection of system and pump curve

106Pumps in parallel
produce flow equal to the sum of the flow of each individual pump at every pressure point; move right along flow rate axis

107Pump in series
sum pressures of each pump, while flow remains unchanged; move directly up the pressure axis

108Throttling (pump/fan) flow rate
reduces flow by closing valve/damper, same power. Adds pressure to system

109Pumps with VFD
reduces flow by reducing frequency -> reducing RPM and power of motor. RPM changes so pump curve changes, parallel to old curve

110Net positive suction head available
1. Open system - $NPSHA=P_{abs} \pm P_{elev} - P_{fric} - P_{vapor}$
2. Closed system - $NPSHA=P_{gauge}+P_{velocity}-P_{vapor}$
111psi to ft head conversion
1 psi = 2.31 ft/SG (in handbook)
1122.31 derivation
$1 psi = \frac{144~\frac {in^2}{ft^2}}{62.4~\frac{lb}{ft^3}} = ft~head $
113velocity head (pumps)
$h_{P_{velocity}}=\frac{v^2}{2g}~[ft~head]$
114Cavitation
static pressure of a liquid reduces to below the liquid's vapor pressure, leading to the formation of small vapor-filled cavities in the liquid. When subjected to higher pressure, these cavities, called "bubbles" or "voids", collapse and can generate shock waves that may damage machinery and piping
115Fan Curve
Should operate within the stable region, as within the unstable region a given pressure value can have multiple CFMs; less change in CFM per change in pressure in stable region

116(Fan) system resistance curve
summation of all friction losses in the ducting system at varying CFMs; intersection of fan curve and resistance curve is operating point

117Explain these curves

1. Red curves show impeller diameters and pressure at varying flow rates
2. Intersection of red curve and blue horsepower curve show horsepower required at operating point
3. Intersection of red and green curve show efficiency at operating point
118Valve function
maintain a set pressure or flow
119Valve types
globe valve - consists of a plug and a seat, where the plug is raised/lowered to increase/decrease flow
ball valve - ball in center of valve can be turned to enlarge or shrink the opening; opening is perpendicular to direction of flow when valve closed
butterfly valve - disc in the center of the valve that can be swung open and closed
120Valve authority
Relationship between flow rate and % open/close status of valve

121Valve coefficient
flow rate through valve in one minute at 1 psi; $C_{v}=\frac{Q}{\sqrt{ \Delta P}}$
122Sizing valves for gases
Equation valid only when change in pressure across valve much less than operating pressure:
$Q~[scfh]=59.64*C_{v}*P_{operating}\sqrt{ \frac{\Delta P}{P_{operating}} }\sqrt{ \frac{520}{SG*T} }$
scfh = standard cubic feet per hour
T = absolute temperature (Rankine)
123Critical Point (valves)
point where flow rate does not change no matter %open/close of valve
124Control Dampers
control flow of air by modulating or two-position control, open/close
125Damper Authority
Determines controllability of the damper; lower the value the less control at higher percentages of max airflow

126How is damper authority determined
dividing pressure drop through damper when open by total pressure drop through ducting (only includes ducting affected by the damper)
127GWP
Global warming potential; reference point is $CO_{2}=1$
128ODP
Ozone depleting potential; reference point is CFC-11 = 1
129Refrigerant types
HCs - hydrocarbons
CFCs - chlorofluorocarbons
HCFCs - hydrochlorofluorocarbons
HFCs - hydrofluorocarbons
HFOs - Hydrofluoroolefins
130How are refrigerants classified
131Name some CFCs
R-12,R-11; contains ozone depleting chlorine and high GWP; phased out in '95
132Name some HCFCs
R-22,R142B; containes ozone depleting chlorine, high GWP; phasing out
133Name some HFCs
R-134a,410A,32; ODP=0 but high GWP
134Name some HFOs
HFO-1234yf; ODP=0 and very low GWP; next gen refrigerants
135Refrigeration cycle components
Expansion valve, accumulator, filter, oil separator, hot gas bypass valve, receiver, filter/dryer, solenoid valve, sight glass

136Accumulator
suction side of compressor after evaporator; accumulates excess liquid from evaporator that can damage compressor
137Filter
placed at evaporator exit; prevents contaminants from entering the compressor
138Oil separator
high pressure side of compressor - removes oil from refrigerant stream collected from oil seals/lubrication to ensure high heat transfer from refrigerant
139Hot gas bypass valve
controlled by compressor inlet temperature; if evaporator temperature too cold, hot gas bypass the condenser and sent to the evaporator to create a false load to prevent frost
140Receiver
after condensor; collects all the refrigerant liquid
141Filter/Dryer
before expansion valve; protects expansion valve by removing contaminants and water moisture that could freeze the expansion valve (expansion valve lowers pressure to turn refrigerant to gas, but could freeze water as well if present)
142Solenoid valve
after filter/dryer and interlocked with compressor; shut-off and open flow through system; when compressor shuts off and solenoid valve closes, separation between high pressure (condenser) and low pressure (evaporator) side
143Sight glass
close to expansion valve - diagnostic tool to see refrigerant quality entering the expansion valve; check if refrigerant is liquid or gas and if frost or moisture forming
144Supply air system components
air handling unit, supply ducting, dampers, terminal units, diffusers
145Equivalent diameters
- Use to convert rectangular ducting to equivalent circle diameter; equations in handbook
- Hydraulic diameter for flow
- Equivalent diameter for duct air flow
146Air handling unit (AHU)
Fan with cooling/heating cools, where exhaust air is replaced with new outside air
147AHU components
(in order)
1. Mixing box - mixes correct amounts of outside air with return air using dampers
2. Air filter - protects following devices and keeps them clean
3. Heating and/or cooling coil - conditions air to correct leaving temperature
4. humidifer/dehumidifier - condition air to correct leaving humidity
5. Fan - provided ahead or behind devices depending on design; if last draw-thru, if first blow-thru
6. Energy recovery device - placed if applicable

148Terminal unit
controls amount and conditions of air distributed to specific space, e.g. VAVs
149Diffusers
control the way air distributed throughout the space; maintain minimum air velocity
150Diffuser selection criteria
noise criteria, throw, velocity
151ADPI
Air diffusion performance index - statistical percentage of points when measured uniformly within space whose draft velocities and temperatures fall within comfort criteria; <80 acceptable
152How to read diffuser table
1-4-way signal how many directions you can throw the air out
numbers in column corresopnd to terminal velocities 150, 100, and 50 ft/min

153Constant volume system
- fans at AHU either on or off
- manual balancing dampers adjusted to supply a set airflow rate through diffuser
based on max design conditions- minimal controls for only one temperature zone

154Constant volume with reheat
heating coil installed in-line with duct to provide sensible heating; only allowed in specific scenarios:
1. One constant volume AH serves multiple rooms with different cooling schedule, but only one space thermostat to control fan; use reheat for more control
2. Reheat coil used to add load to prevent overcooling
155Variable volume system
adds variable frequency drive (VFD) to fan in AHU and VAV boxes in supply air branches to adjust airflow based on cooling demands; reheat included if minimum airflow high enough

156Dual duct system
one duct supplies hot air and other supplies cold air; dual duct VAV boxes connect to both air supplies so can mix in varying proportions

157System controls of variable volume systems
- temperature sensor connect to VAV box controller and modulates damper to adjust cool air flow as needed
- when damper at min position, reheat has override; if open then damper has primary control
- pressure sensor ~2/3rds down the main duct branch to maintain system pressure and airflow rate
- track dampers used to verify sufficient outside air supply (or DOAS used)
158Convert GPM to CFS
$GPM*{\frac{1}{448.83}=ft^3}/s$
159Anchors
supports that restrict movement of pipe in all three dimensions
160L-bend, Z-bend, U-bend parameters
Equations found in handbook for calculating length of these bends to account for stresses
161Air cooled, constant flow chilled water system
rejects heat to ambient air, so piping transports CHWS to air handlers/fan coils units; 3-way valves used to supply CHW to air handler or bypasses

162Water cooled, constant flow chilled water system
rejects heat to water which is brought to cooling tower

163Variable-primary chilled water flow
variable speed pumps to distribute chilled water through a single loop between chiller and air handler

164Primary-secondary chilled water-flow
two chilled water loops; primary loop circulates CHW through the chiller, secondary loop circulates CHW to air handlers

165Direct-return
supplies and returns CHW in the most direct path, where the first AHU to receive and return CHW is closest to the chiller and the last AHU is farthest from the chiller (pressure drop needs to be accounted for from start to end via balancing)
166Reverse-return
equalizes pressure throughout the loop by supplying the AHU closest to the chiller with CHW first, but the last unit to return
167Dual temperature system
distributes both CHW and HW using different piping configurations (two pipe, four pipe, four pipe separate)
168Longest length method
1.convert equipment Btuh value to cubic feet/hour of gas flow using either the HHV (if equipment is condensing) or LHV (if equipment not condensing) of fuel
2. find length of piping from delivery point to most remote outlet
3. Use natural gas pipe sizing table in handbook to get maximum CFH for each pipe size
169Branch length method
1. convert equipment Btuh value to cubic feet/hour of gas flow using either the HHV (if equipment is condensing) or LHV (if equipment not condensing) of fuel
2. for each branch pipe section, take gas flow rate and the total length from that pipe section to the starting point (including length of pipe section too)
3. Use natural gas pipe sizing table in handbook to get maximum CFH for each pipe size
170Sizing steam piping
Use steam pressure drop through piping table in handbook
171Boiler steam system
Efficiency = change in enthalpy between steam and feedbwater over input energy from fuel
$\epsilon_{boiler}=\frac{\dot{m}_{water}*(h_{steam}-h_{feedwater})}{\dot{m}_{fuel}*HHV}$
172Wrap-around Heat Pipe
precool warm humid air by transferring heat to exiting cool supply air; typically used in warm humid climates in spaces with high outside air requirements

173Run-around loop
two heat exchange coils connected by piping, a fluid, and a pump; heat transfer fluid pumped between two coils to transfer heat from one air stream to another
174Air-Side Economizer
two sets of dampers, where one controls the amount of return air directed either to exhaust or back to the AH and another set controls amount of outside air routed to AH
175Gain
ratio of change in output signal to change in input signal
176Chilled water reset
Slowly increase chilled water temperature as load conditions fall (based on return air or outside air)
177Supply air reset
Slowly increase supply air temperature if return air conditions or outside air conditions are met.
178Temperature reset
temperature setpoint modulated by control system to match load of the system
179Economizer
control system controls OA and RA dampers and an exhaust air fan on an AH to use less energy
180ASHRAE 15
Safety Standard for Refrigeration Systems - Lists allowable refrigerant quantities per room volume and other safety considerations; has safety groups for each refrigerant

181Required exhaust to evacuate refrigerant from space
$Q~[CFM]=100G^{0.5}$, where G=max lbs of refrigerant
182ASHRAE 34
Safety Class of Refrigerants - Lists refrigerant safety groups, concentration limits, other refrigerant info
183OEL
occupational exposure limit - concentration of refrigerant a person can withstand for a certain amount of time (~15 minutes)
184LFL
lower flammability limit - lowest concentration (density) of refrigerant in air that can ignite at certain temperature (140F) and pressure (atm)
185ASHRAE 55
Thermal Environment for Human Occupancy - Human comfort limits: draft, temperature, clothing

186ASHRAE 62.1
Ventilation for acceptable Indoor Quality - establishes minimum qualities of fresh air through different types of occupied space to limit recirculation
187ASHRAE 62.1 air classes
- Class 1 - low contaminant concentration (RA from offices, lobbies, libraries)
- Class 2 - moderate contaminant concentration (RA from art classrooms, nail salons, toilets, etc)
- Class 3 - significant contaminant concentration (RA from mechanical rooms, laundry rooms)
- Class 4 - highly objective fumes, dangerous particles, gases (RA from labs and chemical storage)
188ASHRAE 62.2
Ventilation for Indoor Air Quality in Low Rise Residential
189ASHRAE 90.1
Energy Standards for Buildings Except Low Rise Residential Buildings - minimum level of energy efficiency for HVAC systems and other building systems
190ASHRAE 90.2
Energy Standard for low rise residential
191ASHRAE 189.1
Standard for High-Performance Green Building, except Low Rise Residential - More stringent requirements than ASHRAE 90.1
192NFPA 90A
Standard for the Installation of Air-Conditioning and Ventilating Systems - requirements for AC and ventilating equipment w.r.t fire protection
193Smoke index
measure of smoke concentration of a material when it is burning; max allowed is 50
194Smoke damper requirement
smoke damper required at all smoke barriers and should be activated automatically
195Flame spread rating
how well a material burns and spreads a fire; maximum allowed is 25
196Fire damper requirement
fire dampers required at all fire rated walls or partitions of 2 hours or more
197NFPA 90B
Standard for the Installation of Warm Air Heating and Air-Conditioning Systems - provides requirements for ducts, heating panels, boilers, etc.
198NFPA 96
Standards for Ventilation Control and Fire Protection for Commercial Cooking Operations
199Montreal Protocol
plan for phasing out ozone depleting substances like CFC's and HCFC's
200Minimum fresh air flow rate
Definedi n ASHRAE 62.1: $(min)~Fresh~air~flow~rate~(CFM)=R_{p}*(\#~of~people)+R_{A}*(Area)$
- R_P=people fresh air rate (CFM/person)
- R_A=area fresh air rate (CFM/Area)
201MERV
minimum efficiency reporting value for air filters - MERV-6 minimum
202Vibration control
properly isolate or dampen moving parts to avoid damaging equipment and supporting structures
203Vibration isolator selection process
1. Find disturbing vibration frequency (frequency the equipment is vibrating)
- fans, pumps, motors have frequency equal to their RPM (e.g. 1800 RPM * (1 min/60 s) = 30 hz)
- find and use lowest frequency if multiple, since it'll also isolate higher frequencies
2. Choose transmissibility of vibration isolator (amount of vibrations transmitted through isolation system)
$Isolation (\%)=100-Transmissibility (\%)$
3. Find natural frequency of vibration isolator required to achieve this transmissibility
4. Use required natural frequency to select vibration isolator
- consider support weight and deflection amount as well
204Relation between natural, disturbing frequency and transmission
The greater the ratio of $\frac{f_{d}}{f_{n}} > 1.4$, the greater the attenuation of transmissibility (decreases with square of frequency), i.e. vibration isolation improves

205Base/Isolator types
Use selection guide for vibration isolation table in handbook
206Sources of noise in HVAC
HVAC equipment, air turbulence
207Sound power
"Heat source strength": $dB=10\log\left( \frac{W}{1*10^{-12}} \right)$
208Sound pressure
"Resulting temperature": $dB=20\log\left( \frac{x~Pa}{20*10^{-6}~Pa} \right)$
209Sound power and pressure relationship
$Sound~Power=Sound~Pressure+10\log\left( \frac{4\pi r^2}{A_{0}} \right)$
r = distance away from equipment
A0 = reference area (typically 1 m^2 or 1 ft^2)
210Sound table ratings
provide sound levels at range of frequencies
211A-weighting (DBA)
give sound levels at lower frequencies a lower rating since they're not as easily heard by the ear
212Total sound value
$L_{A}=10*\log(10^{DBA_{1}/10}+10^{DBA_{2}/10}+\dots)$; can also be used to combined multiple sources of noise
213NC Rating
Room or space must be lower than all points of a given NC curve to meet that NC rating

214Duct insertion loss
Use duct insertion loss table in handbook to calculate sound power loss over duct lengths
215Sound relation to distance
Sound reduces in proption to distance squared
216Indoor turbulence sound calculations
primarily based on velocity; noise increases with turbulence and exacerbated by elbows, expansions, contractions that cause less smooth flow