Vol. 2

55 flashcardsby LèSpicyPeen
Study these flashcardsFree · spaced repetition · iPhone, Android, Mac & web

All cards

1
What voltage classes can be used for a Distribution System?
5kV, 15kV, 25kV, and 35kV
2
The main substation is usually located as close as possible to.
the center of the base load distribution.
3
Which item is designed to open a circuit automatically under load and then restore the service quickly once the fault has cleared?
Circuit breaker.
4
A substation with one incoming transmission circuit and three outgoing distribution circuits has ( at least ) how many lightning arresters?
12
5
Which item supplies control voltage to operate circuit breakers?
Batteries.
6
In a circuit, the step-voltage regulator's primary and secondary windings are configured with the primary in.
parallel and the secondary in series.
7
What item in an oil circuit breaker suppressed an arc?
Oil.
8
What oil circuit breaker components supply amperage to the protective relays?
Current transformers.
9
The insulating quality is sulfer hexafluoride (SF6), at 0 PSI, is how much greater than dry air?
2 1/2 times.
10
Why are high-voltage fuses enclosed?
To keep melted metal from dropping into nearby equipment.
11
What is installed inside the insulated fiberglass tube assembly to complete the connection between the upper and lower contacts on the fuse holder?
Fuse link.
12
How can a craftsmen easy identify blown fuse cutout?
A cutout door is hanging down.
13
What percent of electrical system faults are temporary?
95.
14
Which of these devices does not interrupt a fault current?
Sectionalizer.
15
Where are overhead switches normally mounted?
On substation structures or utility poles.
16
What is required for a gang operated overhead switch on a 3-phase circuit?
Three sets of blades and contacts.
17
What is usually installed with an oil circuit breaker to allow for equipment maintenance and allows you to keep the circuit in operation?
Knife blades and normally open air-break switch.
18
The oil in oil circuits breakers is checked dielectrically.
every 6 months.
19
Strong odor from the gas in a sulfur hexafluoride circuit breaker is an indication that.
gas decomposition has taken place.
20
Clean a modern air switch that has been closed for a long time by.
opening and closing the switch several times.
21
Battery bank maintenance is normally done.
every month.
22
What is used to test a battery cell for its specific gravity?
Hydrometer syringe.
23
Switchboard graphic instruments and revenue watt-hour meters must be calibrated every.
4 years.
24
Which device is essentially a voltage regulator and requires similar servicing?
Distribution transformer.
25
The maintenance interval for voltage regulators is every.
year.
26
Battery electrolyte impurities cause.
Irregular cell operation.
27
After repair work on a relay you must.
make a complete performance test.
28
What publication outlines how to perform a flash hazard analysis to determine personal protective equipment requirement?
National Fire Protection Association (NFPA) 70 E.
29
Leather protectors or gauntlets should be.
2 to 5 inches shorter than the rubber gloves.
30
Which of these combinations are you likely to use inside rubber gloves?
Cotton gloves and dusting powder.
31
The supervisor must visually inspect rubber blankets every.
6 months.
32
How must rubber blankets be stored?
Flat or rolled in blanket canister.
33
While working, what must be done if your rubber gloves come in contact with petroleum based products?
Wipe them off quickly.
34
While inspecting rubber insulating lines hoses, which condition would require the line hose to be removed from service?
Damage extending 1/4 of the wall thickness.
35
What is used to clean nylon parts of body work positioning equipment?
Mild soap and water.
36
When leather cannot be made soft and pliable enough by saddle-soap dressing, it should be.
oiled
37
Which part of the gaff do you sharpen?
Flat inner side.
38
How should you plan your climbing route with respect to single crossarm?
Opposite the crossarm.
39
When two workers are ascending a pole, the second worker must not start climbing until.
The first one is in a safe work position.
40
Which of the following manufacturer's certification tests is acceptable for hotsticks?
100,000 volts AC per foot 5 minutes on fiberglass and epoxy sticks.
41
Hot sticks are electrically tested with a.
direct current (DC) hi-pot test set.
42
How long is the 100-kilovolts (kV) test voltage applied to a hot stick?
1 minute
43
At the job site, the aerial lift device should be positioned so the work area is always.
within reach of the boom.
44
Materials or tools can only be passed from a worker on the ground to a worker on the aerial lift vehicle when.
both workers are wearing rubber gloves.
45
The test voltage for an aerial lift basket test is.
100 kilovolts (kV) direct current (DC).
46
The line truck winch is operated
through the power takeoff.
47
How is the rope put on the capstan?
Wind it clockwise, with the load end next to the truck.
48
The purpose of hand signals is to ensure
clear communication between truck operator and ground worker.
49
What does holding up a closed fist indicate?
Stop all action.
50
Which of these is Operator's Inspection Guide and Trouble Report (Aircraft Towing, Base Maintenance, Deicers, High Reach and Snow Removal), on which you write up line truck inspection discrepancies?
AF Form 1800
51
What is the more common name for a constant current transformer?
Constant current regulator.
52
The insulation value of transformer coils, bushings, and oil determines
The voltage rating of the transformer.
53
When you make a delta-delta connection for lights and power, there is one unusable voltage from
B phase to C phase.
54
Which meter do you use in a transformer continuity check?
Megger.
55
Which connection would you use for a continuity check on the primary winding of a transformer?
H1 to H2.
Study all 55 cards for free